1
 
1 | 2
 
 
PRS1000 Series Rectifier
 
 
 
 
SMPS1002L / SMPS1004L
SMPS1002M / SMPS1004M
SMPS1002H / SMPS1004H
 
 

PRS1000 Series Rectifier Specification
 
 
Model
SMPS1002L/SMPS1004L
SMPS1002M/SMPS1004M
SMPS1002H/SMPS1004H
  Input
  Rated voltage
220 V
  Operation range
110 V ~ 310 V
100 V ~ 300 V
  Overvoltage protection
  If the mains exceed 300 (310) V, it will be shut off automatically; while the mains
  return to 285±10V, it will be restored automatically.
  Undervoltage protection
  If the mains are under 100 (110) V, it will be shut off automatically; while the mains
  return to 110(120)V, it will be restored automatically.
  Current
≤6A
≤8A
≤10A
  Frequency
50/60 Hz±10%
  Power Factor
≥0.995
  Output
  Voltage
24V (20~29 V adjustable)
48V (40~58 V adjustable)
48V (40~58 V adjustable)
  Current
20A (48V)
40A (24V)
25A (48V)
50A (24V)
30A (48V)
60A (24V)
  Current sharing at paralleling
≤±5%
  Voltage stability precision
≤±0.5%
  Protection
  Overvoltage of input, overvoltage of output, overcurrent, lowvoltage, short-circuit and
  over temperature.
  Other Data
  Efficiency
≥91%
  Cooling mode
Natural cooling
System fan cooling
Fan cooling
  Operation temperature
-10~+55°C
  Storage temperature
-40~+85°C
  Degree of protection
IP20
  Ripple voltage
≤200m Vpp
  Phosphometric noise
≤2m V
  Reliability
MTBF>10^5h
  Load effect (load regulating
  ratio)
≤±0.5%
  Restoring time of load effect
  (dynamic response)
≤200 μ s
  Source effect (line regulating
  ratio)
≤±0.1%
  Soft start time
≥3s
  Dimension
66.8mm (W) x 220mm (D) x 264mm (H)
75mm (W) x 258mm (D) x 264mm (H)
  Weight
2.8 kg
3.4 kg
  Electromagnetic Compatibility
  Conduction
  AC input in accordance with EN50081-1 and EN50081-2 standards, DC output in
  accordance with EN50081-2 standard.
  Radiation
  In accordance with EN50081-1 and EN50081-2 standard.
  Anti-interference
  In accordance with EN50082-1 and EN50081-2 standard.
  Safety
  In accordance with IEC950, EN60950, EN41003, UL1950, and AS/NSZ3260 standards
  Insulation Feature
  Insulation resistance     >2MΩ
  Input to ground            1.5 K V
  Input to output             1.5 K V
  Output to ground          710 V
 
     
   
 
 
 
AL175NT Control Module
  • LCD displays system information, alarm, operation menu.
  • LED indicator displays system integrated alarm and system status.
  • With RS232 interface, able to connect PC or Modem
  • Provide battery equalizing charging control
  • Battery on-line discharging test automatically or manually
  • Temperature compensation function for battery charging
  • Load disconnects automatically while battery is low voltage
  • Battery midpoint voltage symmetry monitor and test function
  • Monitor software can be used in WINDOW
  • Dimension: 70.8 mm (W) x 169 mm (D) x 128.4 mm (H)
  • Weight: 0.8kg
PR1000ML Sub-rack
  PR1000ML sub-rack can be installed with 7 SMPS1002L, SMPS1004L, or SMPS1004M
  rectifier modules. AC/DC distribution and integrated transmission system information
  can be processed by single circuit board.
PR1000H Sub-rack
  PR1000H sub-rack can be installed with 6 SMPS1004H rectifier modules. AC/DC
  distribution and integrated transmission system information can be processed by
  single circuit board.
 
 
 
 
   
 
1 | 2
 
   