1
 
1 | 2
 
 
PRS2000 Series Rectifier
 
 
SMPS2000 Rectifier Module
 
 

PRS2000 Series Rectifier Specification
 
 
Model
SMPS2000 Rectifier Module
  Input
  Rated voltage
Single phase 220 V
  Operation range
130 V ~ 300 V
  Overvoltage protection
  If the mains exceed 300 V, it will be shut off automatically; while the mains return to
  285±10V, it will be restored automatically.
  Undervoltage protection
  If the mains are under 130 V, it will be shut off automatically; while the mains return to
  130 V, it will be restored automatically.
  Current
≤15A
  Frequency
50/60 Hz±10%
  Power Factor
≥0.995
  Output
  Voltage
48V (42~59 V adjustable)
  Current
50A
  Current sharing at paralleling
≤±5%
  Voltage stability precision
≤±0.5%
  Protection
  Overvoltage, overcurrent, lowvoltage, short-circuit and over temperature.
  Other Data
  Efficiency
≥91%
  Cooling mode
Fan cooling
  Operation temperature
-10~+55°C
  Storage temperature
-40~+85°C
  Degree of protection
IP20
  Ripple voltage
≤200m Vpp
  Phosphometric noise
≤2m V
  Reliability
MTBF>10^5h
  Load effect (load regulating
  ratio)
≤±0.5%
  Restoring time of load effect
  (dynamic response)
≤200 μ s
  Source effect (line regulating
  ratio)
≤±0.1%
  Soft start time
≥3s
  Dimension
130mm (W) x 423mm (D) x 266mm (H)
  Weight
11 kg
  Electromagnetic Compatibility
  Conduction
  AC input in accordance with EN50081-1 and EN50081-2 standards, DC output in
  accordance with EN50081-2 standard.
  Radiation
  In accordance with EN50081-1 and EN50081-2 standard.
  Anti-interference
  In accordance with EN50081-1 and EN50081-2 standard.
  Safety
  In accordance with IEC950, EN60950, EN41003, UL1950, and AS/NSZ3260 standards
  Insulation Feature
  Insulation resistance     >2MΩ
  Input to ground            1.5 K V
  Input to output             1.5 K V
  Output to ground          710 V
 
     
   
 
 
 
CU2000 Control Module
  • Adopt LCD display of large size, and display of Chinese directly
  • Able to control by keyboard
  • With complete alarm, automatic protection function, able to produce acoustic and
     visional alarm.
  • Battery monitor function:
Period, manual, automatically equalizing, floating charging change
Battery on-line discharging test
Battery charging voltage temperature compensation (optional)
Battery charging current limitation
Battery overdischarging protection and twice power supply protection
  • With function of environment monitor and test (including environment temperature
     smog alarm, optional)
  • Input: 8 analog inputs, 8 digital inputs
  • Output: 12 relay outputs, 1 digital output, 1 analog voltage output
  • Support directly MII centralized monitor communication protocol
  • Adopt standard RS232 interface
  • Dimension: 210 mm (W) x 173 mm (D) x 133 mm (H)
  • Weight: 1kg
PR2000 Sub-rack
  • PR2000 sub-rack can be installed with 4 rectifier modules.
  • AC/DC distribution and intergrated transmission of system information can be
     processed by single circuit board.
  • AC input connection distribution
  • DC join togethers
  • Communicate with control module
PRS2000R2 Integrated Rack
  The system includes: 2 PR200 rectifier module sub-racks, 8 SMPS2000 rectiifier
  modules and 1 CU2000 control module. The output is up to 400A.
 
  AC Distribution
  AC auxiliary output: three phase 16Ax2
  DC Distribution
 
Low resistance distribution
High resistance distribution
  Load shunt
Fuse 300A x 2,100A x 4
Fuse 300A x 2,100A x 4
Fuse 36A x 2,16A x 6
Fuse 16A/45mΩ x 54
  Battery shunt
Fuse 400A x 2
Fuse 400A x 2
  Lead-out mode
Upper lead-in
Upper lead-out
Upper lead-in
Upper lead-out
  Other data
  Dimension
600 mm (W) x 600 mm (D) x 1600 mm (H)
600 mm (W) x 600 mm (D) x 2000 mm (H)
  Weight
200 kg (not include rectifier module)
250 kg (not include rectifier module)
 
 
 
 
   
 
1 | 2
 
   